Your Browser is not longer supported

Please use Google Chrome, Mozilla Firefox or Microsoft Edge to view the page correctly
Loading...

{{viewport.spaceProperty.prod}}

Switching the SE server off

The following hardware components must be switched off in the specified order.

CAUTION!

This does not disconnect the hardware components completely from the power source (POWER STAND-BY). To cut the entire system off from the power source, you must must disconnect the power distribution units from the power source
Notify Customer Support.

1. Switch off the optional Application Units

Before an Application Unit is switched off, the power-on indicator lights up green.

>

Terminate the customer applications and the operating system properly.

The Application Unit is switched off automatically and enters standby mode.
The status indicator lights up orange. Check this before continuing.

If the operating system does not automatically switch off the Application Unit, hold the On/Off switch down for at least four seconds.

Alternatively, as the administrator or AU administrator you can switch the Application Unit off using the SE Manager (menu Hardware  -> Units -> <se server> ] (SE<model>), Units tab, Switch off symbol), see the “Operation and Administration” manual [5].

The controls, indicators and further on/off options for the AU are described in the "Additive Components" Operating Manual [4].

Further Application Units are switched off in the same way.

2. Switch off the Server Unit

>

As the administrator, BS2000 administrator or a privileged operator, switch off the Server Unit using the SE Manager (menu Hardware ->
Units -> <se server> ] (SE<model>), Units tab, Switch off symbol), see the “Operation and Administration” manual [5].

When the Server Unit is switched off, the BS2000 system is shut down properly taking into account the remaining runtime specified.

Before the Server Unit is switched off, the power-on indicator lights up green, and after it has been switched off, it lights up orange. Check this before continuing.

The controls and indicators of the Server Unit are described in the "Server Unit x86" Operating Manual [3].

Further Server Units are switched off in the same way.

3. Switch off the MU

>

Switch off the MU using the SE Manager (menu Hardware -> Units -> <se server> ] (SE<model>), Units tab, Switch off symbol), see the “Operation and Administration” manual [5]

Before the MU is switched off, the power-on indicator lights up green, and after it has been switched off, it lights up orange (item 11 in figure 10). Check this before continuing.

4. Switch off the optional hardware components

>

Switch off the ETERNUS LT40 S2 tape library using the On/Off switch on the front (see the "Additive Components" Operating Manual [4]).

>

Switch off any other connected hardware components.

The ETERNUS JX40 S2 disk storage system connected to a Server Unit is switched off automatically when the Server Unit is switched on/off.