Your Browser is not longer supported

Please use Google Chrome, Mozilla Firefox or Microsoft Edge to view the page correctly
Loading...

{{viewport.spaceProperty.prod}}

Installation and operation precautions

&pagelevel(3)&pagelevel

CAUTION!
Equipment damage

Be sure to follow the precautions below when installing or operating the equipment.
Otherwise, the SE server may be damaged.


Installation precautions

WARNING!

The SE server is installed on the vendor’s premises. Modifications may only be carried out by Customer Support. The customer may not make any changes to the server!

The following section is therefore for information purposes only.

Follow the instructions below to ensure safety when positioning the SE server:

  • The Server Unit, Management Unit, Application Units and further components are installed in one or more closed racks. Consequently the ambient operating temperature inside the rack may be higher than the room temperature. Install the business server in an environment in which the ambient temperature is always below 35 °C (95 °F).

    • Adjust air circulation to prevent the temperature inside the rack from exceeding the maximum ambient temperature specified for the server components.

    • The maximum allowable operating temperature of the server components is 35°C (95 °F).

  • A certain amount of air flow is required for safe operation of the server components.

    • The server components have ventilation openings at the front and rear. Do not cover or close the ventilation openings. Doing so may cause the server components to overheat.

  • Positioning the Business Server may cause the entire rack to be unstable because of uneven mechanical loading.

  • The racks of the SE server have no stabilizer. When an SU or heavy peripherals are pulled out of the rack, there may therefore be a risk of it tipping over.

  • The power supply for the server components is implemented via power distribution units mounted in the rack which themselves must be connected to the inhouse power supply using appropriate CEE connectors.

  • The large number of power supply components in the rack means that the configuration can generate leakage currents > 3.5 mA.

  • For this reason the rack may be connected to the in-house power network only via permanent links or industrial cables in accordance with IEC 60309 (formerly IEC 309) .

CAUTION!
Equipment damage

In configurations with multiple feed cables such as the SE server, it must be noted that all cables must be disconnected to disconnect the system from the power network.


Operating precautions

WARNING!
Danger of electric shock and fire

  • Do not damage, break or modify the cables. Cable breaks can cause electric shocks and fires.

CAUTION!
Equipment damage

  • Do not cover or block ventilation openings.

  • Install the SE server in a location away from direct sunlight and sources of heat.

  • Install the Server Unit in an environment free of dust, corrosive gases, and salt air.

  • Install the business server in a location free of vibration and on an even surface to prevent the business server from leaning.

  • Do not run any cable beneath any equipment. Also, prevent cables from becoming taut. Never disconnect the power cable of the Server Unit while power is being supplied to the SE server.

  • Keep objects off the rack and the rack components. Never use the rack as a work area.

  • Do not allow condensation to form. In winter, slowly raise the ambient room temperature to prevent condensation from forming in the Server Unit.

  • Use the SE server only after it has warmed up sufficiently.

  • Operate the SE server away from noise-generating sources, such as photocopiers, air conditioners, and welding equipment.

  • Take preventive measures to control electrostatic buildup. Note that carpets often generate static charge which may cause the SE server to malfunction.

  • When moving the business server, do not pull on the front cover. Doing so may cause damage to the SE server.